PG5908A
Industrial Rack-mount DNP3, Modbus, IEC 60870, IEC 61850 Protocol Gateway with 8 Sw-Selectable RS232/485/422 RJ45 serial ports, 6 Fast-Ethernet ports, IEC 61850-3 certified
- Compliant with IEC 61850-3 and IEEE 1613 Power Substation Standards
- 8 or 16-port RS-232/422/485, baud rate up to 921.6 Kbps
- Isolated redundant power inputs with 24-48 VDC ,100-240 VAC, 100-370 VDC variations
- Works in environments from -40 to 85°C
- Same hardware platform for different protocol conversion (Modbus TCP/RTU/ASCII, DNP3.0 TCP or serial, IEC 60870-5-101, IEC 60870-5-103, IEC 60870-5-104, IEC 61850)
- User friendly configuration with a Java-Based Windows utility
The PG5908A/PG5916A Series is a highly reliable and fault tolerant Industrial Protocol Gateway. Its powerful architecture provides seamless conversion between the different protocols Ethernet or Serial based. The serial devices communicating on different protocols could be integrated into the system and extend its reach over the gateway’s redundant Ethernet. This device is designed to work in most demanding industries such as power substations, power generation, oil and gas, farming and manufacturing.
The configuration carried out through a use friendly, Java- Based Windows Utility called eNode Designer. It allows configuring target platforms, set device properties and protocol data point mapping. To do so, a project file representing the system should be created. This will include devices and the protocol applications running on them. The configuration is completely dependent on the “eNode Module” which represents that device or application – but may include things such as changing the communication port settings and defining where data point information enters and leaves the eNode Designer system.
Hardware Specifications | |
Network Interface | |
Ethernet Port | 6x RJ-45 or 6x SFP slot |
LAN Mode | Dual Subnets or LAN Redundancy |
Compliance |
IEEE 802.3 10 BASE-T
IEEE 802.3u 100BASE-T(X) and 100 BASE-FX |
Serial Interface | |
Connector | 5-Pin 5.08mm Terminal Blockor D-Sub 9 connector |
Port | 8 or 16 |
Mode | RS-232/422/485,software selectable |
Baud Rate | 50~921,600bps |
Parity | None,Odd,Even,Space,Mark |
Data Bits | 5,6,7,8 |
Stop Bits | 1,2 |
Flow Control | None,Xon/Xoff,RTS/CTS(RS-232only) |
Power Characteristics | |
Connector | 10-Pin Terminal Block |
Input Voltage |
24-48VDC
100-240VAC / 100-370VDC for HV Series |
Power Consumption |
0.73A @ 24VDC
0.35A @ 100VAC 0.2A @ 100VDC |
Power Redundancy | Yes (Two Modules) |
Reverse Polarity Protection | Yes |
Mechanicals | |
Housing | IP30 protection,metal housing |
Dimensions(WxH xD) | 440.6mm x 44mm x 309mm |
Installation | 19”Rack Mount |
Reset Button | Yes |
Weight | 4kg |
Environmental Limits | |
Operating Temperature | -40°C~85°C(-40°F ~185°F) |
Storage Temperature | -40°C~85°C(-40°F ~185°F) |
Ambient Relative Humidity | 5~95%RH,(non-condensing) |
Software | |
Protocols | IPv4, ARP, ICMP, TCP, UDP,DHCPClient,DNS Client, Telnet, HTTP, SNMPv1/v2c,
Sys log |
Regulatory Approvals | ||||
Safety | EN61010-2-201 | |||
EMC |
FCCPart15, Subpart B, Class B
EN55032,Class B EN61000-6-2, Class B EN61000-3-2 EN61000-3-3 EN55024 EN61000-6-4 IEC 61850-3 /IEEE1613 |
|||
Test | Item | Value | Level | |
IEC 61000-4-2 | ESD | Contact Discharge
Air Discharge |
±8KV
±15KV |
4
4 |
IEC 61000-4-3 | RS | Enclosure | 10V/m | 3 |
IEC 61000-4-4 | EFT | AC PowerPort
DCPowerPort Signal Port |
±4.0KV
±4.0KV ±4.0KV |
4
4 4 |
IEC 61000-4-5 | Surge | AC PowerPort
AC PowerPort DCPowerPort DCPowerPort Signal Port |
Line-to Line±2.0KV Line-toEarth±4.0KV
Line-to Line±1.0KV Line-toEarth±2.0KV Line-to Line±2.0KV |
4
4 3 3 4 |
IEC 61000-4-6 | CS | AC PowerPort
DCPowerPort Signal Port |
10Vrms
10Vrms 10Vrms |
3
3 3 |
IEC 61000-4-8 | PFMF | Enclosure | 100A/m | 5 |
IEC 61000-4-10 | Damped
Oscillatory MagneticField |
Enclosure | 100A/m | 5 |
IEC 61000-4-11 | DIP | AC PowerPort | – | – |
IEC 61000-4-12 | Damped
Oscillatory |
AC PowerPort
Signal Port |
2.5KV common,1 KV
differential 2.5KV common,1 KV differential |
3
3 |
Shock | MIL-STD-810FMethod516.5 | |||
Drop | MIL-STD-810FMethod516.5 | |||
Vibration | MIL-STD-810FMethod514.5C-1& C-2 | |||
RoHS | Yes | |||
MTBF | TBD | |||
Warranty | 5years |